Sign In | Join Free | My infospaceinc.com
infospaceinc.com
Products
Search by Category
Home > EL Products >

MTL5573 Intrinsically Safe Isolating Temperature Converter

Categories MTL Instruments
MOQ: 1
Packaging Details: carton
Fuse Rating: 100 mA
Certification: ATEX
Place of Origin: India
Communications Supported: HART terminals 1 & 2 only
Model Number: MTL5573
Current Limit: 48mA minimum
Payment Terms: T/T,Allipay,paypal
Low Power: Battery-powered devices
Signal Range: 4 to 20mA
Price: Negotiable
Relay Type: Single pole, changeover contacts
Power Supply: AC or DC power supply
Supply Ability: 100pcs per month
Resistance: No resistance introduced into loop
Brand Name: MTL
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

MTL5573 Intrinsically Safe Isolating Temperature Converter

MTL5573 Intrinsically Safe Isolating Temperature Converter


Description:

Manufacturer : MTL

Product No. : MTL5573


https://www.achievers-automation.com More Products


Reliable Industrial Component Sourcing for Enterprises

This industrial automation component is supplied for enterprise procurement .Made-to-order and forward delivery are supported, with pricing quoted per inquiry.

To reduce sourcing risk, each order is handled individually with support for model confirmation, condition clarification, and lead time estimation before order placement. Clear quotation terms and consistent communication are provided to help partners manage expectations and complete transactions with confidence. Additional verification or clarification is available when required, supporting professional procurement and long-term cooperation.



The MTL MTL5573 is a compact single-channel galvanically isolated temperature converter belonging to the MTL5500 series of intrinsically safe isolators, manufactured by Eaton MTL Instruments. It converts low-level temperature signals from RTD or thermocouple (THC) sensors installed in explosive hazardous zones into standard 4–20mA analog outputs for safe-side DCS, PLC and recording equipmentAlibaba.co....

This unit provides full 3-port galvanic isolation between hazardous sensor side, safe control side and power supply, eliminating ground loop interference and transient cross-coupling. It supports software-configurable linearisation, sensor ranging, fault diagnostics and cold junction compensation (CJC) for thermocouple inputs. The narrow 16mm DIN rail form factor enables high-density cabinet installation, with certified intrinsic safety approvals for Zone 0 / Class I Div 1 hazardous locations in oil & gas, chemical and pharmaceutical plants. Integrated sensor failure detection outputs configurable upscale/downscale NAMUR NE43 out-of-range signals for alarm logic systems.


Detail:

Parameter ItemOfficial MTL5573 Datasheet Value
Full Model CodeMTL5573
BrandMTL Instruments (Eaton Crouse-Hinds)
Channel Count1 single channel
Supported Hazardous Side InputsAll thermocouple types (J,K,T,E,R,S,B,N,XK); 2/3/4-wire RTD (Pt100/Pt500/Pt1000, Cu/Ni); mV low-level signals
RTD Nominal Excitation Current200 µA
Thermocouple Max Lead Resistance600 Ω
Cold Junction Compensation (CJC)Software selectable ON/OFF; CJC error ≤ 1.0 °C
Standard Output Signal4–20 mA, max load resistance 600 Ω
Out-of-Range StandardConfigurable MTL or NAMUR NE43 fault characteristic
Calibration Accuracy (+20 °C)THC/mV: ±15 µV or ±0.05% input (whichever greater)

RTD: ±80 mΩ

Output: ±11 µA
Rejection PerformanceCommon mode rejection: 120 dB (240 V 50/60 Hz)

Series mode rejection: 40 dB (50/60 Hz)
Power Supply Input24 V DC nominal (20–35 V DC operating range)
Max Current Consumption50 mA @ 24 V DC (20 mA output)
Max Power Dissipation1.2 W @ 24 V DC
Isolation Barrier Rating3-port full galvanic isolation; Um = 253 V rms / DC


Specification CategoryDetailed Technical Data
Mounting Standard35 mm EN 60715 standard DIN rail
Module Dimensions (W × H × D)16 mm × 99 mm × 110 mm slim compact housing
Net Unit Weight115 g
Housing MaterialFlame-retardant yellow thermoplastic
Terminal TypeScrew clamp terminals for field instrument wiring
Operating Ambient Temperature-20 °C ~ +60 °C
Storage Temperature Range-40 °C ~ +80 °C
Intrinsic Safety CertificationsATEX Ex ia IIC T4, IECEx, FM Class I Div 1 / Div 2
Hazardous Zone CompatibilityZone 0, Zone 1, Zone 2; Groups A-D
Intrinsic Safety ParametersUi = 30 V, Ii = 200 mA, Pi = 1.2 W, Ci negligible
Diagnostic IndicatorYellow LED alarm for sensor break / open circuit fault
Configuration MethodPC software via dedicated configuration socket
Industrial Compliance StandardsEN 61010-1, EN 61326-1 EMC, RoHS compliant



Brand



MTL (Measurement Technology Limited) is a British company focusing on industrial automation safety and explosion-proof technology. It was founded in 1955 and is headquartered in Manchester. Currently, MTL is a brand under Eaton Corporation, and is affiliated with Eaton's CrouseHinds product portfolio, focusing on providing intrinsic safety solutions for hazardous industrial environments.

As the world's leading power management company, Eaton further strengthens its competitiveness in the fields of industrial process control, explosion-proof equipment and safety grids by acquiring and integrating MTL's technology and product lines. MTL's product line (such as safety gates, isolation gates, surge protectors, etc.) has now become a core component of Eaton's industrial automation field.



Company Introduction:

Achievers Automation Limited has more than 10 years experience in the market of Industrial Automation, specialized in reselling factory sealed Probe, Sensor, DCS,isolator barrier, HMI, PLC,Adapter,Profibus connector and cable from Brands as BENTLY NEVADA, E+H, MTL, AB, , YOKOGAWA, ASCO, Schneider, Lenze, Pro-face, Mitsubishi, Omron, Lenze, Delta, IFM etc. If you have any request, please do not hesitate to contact us.



Below are the TOP BRANDS we handle in the past 14 years:

FAQ of Achievers

Q:Are the Products Genuine OEM Units?

A: These items have been certified by Achievers Automation Limited to be genuine OEM Units obtained through OEM or independent third-party channels.

Q:How will you arrange shipment?

A: We can arrange shipment based on your request. We have cooperated forwader who can arrange shipment via FedEx, DHL,TNT with good price.

Q:What is the warranty of goods?

A: One-year Warranty.

Buy  MTL5573 Intrinsically Safe Isolating Temperature Converter  at wholesale prices
Send your message to this supplier
 
*From:
*To: Achievers Automation Limited
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0