The IPSYS01 System Power Module is a rack-mounted circuit board
that provides essential operating voltages for industrial control
systems. It supplies 5 VDC, 15 VDC, and -15 VDC to rack I/O
devices, along with 24 VDC power to the cabinet for field I/O. The
module offers flexible input power compatibility, accepting 120
VAC, 240 VAC, or 125 VDC inputs.
For AC inputs, the module incorporates active power factor
correction, achieving a power factor greater than 0.95. It features
current sharing circuitry that enables multiple system power
modules to equally distribute output current without overloading
individual units.
The IPSYS01 includes comprehensive self-monitoring capabilities,
continuously monitoring DC-to-DC converters and the power factor
corrector to ensure reliable operation.

Key Features & Benefits
Versatile Power Distribution
Supplies operating voltages to both Harmony block and rack
equipment
High Availability
Supports selectable N, N+1, N+x, and 2N power supply redundancy
configurations
High Output Capacity
260 watts per module reduces the number of modules required in
system designs
Active Load Sharing
Ensures all power modules share the load equally for balanced
operation
Flexible Input Options
Accepts 120/240 VAC or 125 VDC inputs, with mixed AC and DC inputs
possible in 2N redundancy
Power Factor Correction
Reduces upstream infrastructure investments including electrical
distribution and UPS requirements
Comprehensive Monitoring
Monitors AC/DC inputs, system I/O and bus voltages, cabinet
temperatures, auxiliary channels, and contact inputs
Online Replaceable
Power supply modules and fans can be replaced while the system
remains operational

Rack-Based Control Systems
Powering rack-based control systems in the ABB Bailey Infi 90
series
Industrial Process Automation
Ideal for industrial process automation plants requiring high
availability power supply with redundancy
New or Retrofit Installations
Suitable for new installations or automation cabinet retrofits
where multi-rail DC power and I/O supply are needed