Sign In | Join Free | My infospaceinc.com
infospaceinc.com
Products
Search by Category
Home > Plastic Processing Service >

IEC61850 UPS Battery Testing System Remote Storage Capacity Verification System

Categories Battery Testing System
Payment Terms: T/T
Place of Origin: Shenzhen,Guangdong province,China
Brand Name: OEM / ODM
Price: RMB 49999 per set
Certification: CE / FCC / RoHS
Delivery Time: 7-30 work days
Supply Ability: 10000+
Model Number: SH-RSCVS
MOQ: 10 PCS
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

IEC61850 UPS Battery Testing System Remote Storage Capacity Verification System

Remote Battery Capacity Verification System with Segmental Monitoring 0.1C Discharge and Intelligent Charging for Power Plants


Remote Storage Capacity Verification System
System Definition

Capacity verification through discharge testing remains the most widely recognized method for evaluating battery power capacity. However, traditional on-site verification procedures are cumbersome and consume significant human and material resources, leaving current staffing levels insufficient to meet regulatory maintenance requirements. The remote capacity verification system significantly streamlines this process, enabling efficient completion of battery capacity assessment through discharge testing.

Application Description

Primarily designed to provide AC uninterruptible power supply for various automated systems, signaling devices, communication networks, remote control execution systems, and emergency lighting equipment in critical facilities such as power plants and substations.

System Functional Features
  • The nuclear power system employs battery segmental monitoring technology to ensure uninterrupted DC bus voltage even when individual cells are open-circuited or under-voltage conditions.
  • Monitor parameters including cell internal resistance, interconnect resistance, cell voltage, cell temperature, cell group voltage, and cell group current.
  • Utilize a bidirectional converter module (PCS) to achieve 0.1C (adjustable) grid-fed nuclear capacity discharge, with pre-charging performed before the battery connects to the bus after discharge completion.
  • The nuclear reactor main unit features intelligent charging management capabilities, which prevent battery overcharging and thermal runaway incidents while monitoring the battery open-circuit voltage.
  • Integrated design of the operation and maintenance host; the host communicates with platform software via TCP/IP and supports IEC 61850.
  • Provide a three-tier management platform at the provincial, regional, and station levels, with integrated deployment of DC power monitoring functionality.
  • Utilizes BOOST+LLC isolation boost technology, with parallel CAN connections between isolated power modules achieving a conversion efficiency of over 93%.
  • Maintain the original relationship between the battery pack and the DC busbar without introducing additional fault points; equipped with a manual maintenance bypass switch.
  • The discharge diode features a redundant backup design with an open-circuit detection function.
  • The modular design offers flexible functional combinations, enabling it to independently or simultaneously meet users requirements for "remote battery capacity verification" and "DC bus voltage protection".
Electrical Characteristics
Order NumberProjectTechnical ParameterRemarks
1DC rated voltage85%-120%
2Power supply for the battery cell voltage acquisition moduleDC1.5-24V±10%
3Measurement range for the voltage of a 2V battery1.5--3VA reliable alarm shall be triggered when exceeding the measurement range; the measurement accuracy is ≤ ±0.2%, and the reading value increases by +1 mV.
Measurement range for the voltage of a 12V battery8--15V
4Measurement range for the total current of the battery pack0-350.0VMeasurement accuracy: 50-300 V/≤±(0.5% * reading value + 0.1 V)
5Measurement range for the total current of the battery pack-100--+100AMeasurement accuracy ≤ ±(1%, reading ±0.5 A)
6Temperature measurement range for the negative electrode column of a single cell-10-80℃Measurement accuracy ≤ ±1°C
7Internal resistance measurement range for a single cell (2 V)40~3000mWMeasurement accuracy ≤ (2.5%, reading +15)±mW
Internal resistance measurement range for individual cells (1-2 V)1500~15000mWMeasurement accuracy ≤ (2.5%, reading +90). Repetition accuracy of internal resistance: 2%.mW
8Measurement range and accuracy of the battery connection resistance5~1000mWMeasurement accuracy ≤ (2.5%, reading 5)±±mW
9Measurement cycle for the internal resistance of individual cells and the connection resistance of batteries1 day - 12 monthsThe default cycle is 1 month
10Discharge current current stabilization accuracy10-hour nuclear capacity periodThe discharge current remains stable at I.10After discharge completion, the current stabilization accuracy shall not be less than 2%.
11Load Environment Temperature Sampling Frequency≤5s