Sign In | Join Free | My infospaceinc.com
infospaceinc.com
Products
Search by Category
Home > Baby Toys >

Multi-Function Transformer Power Tester, Portable High Accuracy for Load & No-Load Test

Categories Transformer Tester
Brand Name: MINGYANG
Model Number: MYRS-II
Place of Origin: China Mainland
MOQ: 1
Price: 2200usd
Payment Terms: L/C,D/A,D/P,T/T,Western Union
Supply Ability: 1000pcs/month
Delivery Time: 1 week
Packaging Details: carton
Warranty: 2 Years
Customized support: OEM
Place of origin: Hubei, China
Line voltage: 0-800V
Power supply: AC220V± 10%, 45-55Hz
Capacity: 30kVA-2500kVA (for 10kV oil and dry transformers)
Voltage accuracy: ±0.2%FS at 20-100V; ±0.2%+3 digit at 100-450V
Power: Electronic
Current accuracy: ±0.2%FS at 0.5-10A; ±0.2%+3 digit at 10-100A
Current range: 0-100A
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Multi-Function Transformer Power Tester, Portable High Accuracy for Load & No-Load Test

Electronic Power Comprehensive Analyzer Transformer Load No-Load and No Load Tester
The MYRS-II Transformer Power Tester is a multifunctional measuring instrument that combines the capabilities of both a Transformer Capacity Tester and Transformer Characteristic Parameter Tester. This advanced device accurately measures power frequency parameters including capacity, type, no-load current, no-load loss, short-circuit (load) loss, and impedance voltage for various transformers.
This instrument features compact design, lightweight construction, high measurement accuracy, excellent stability, and simple operation. It completely replaces traditional multi-meter methods for measuring transformer loss and capacity, offering simplified wiring and convenient testing and recording capabilities that significantly improve work efficiency.
Key Features
  • Accurate measurement of various distribution transformer capacity
  • Comprehensive testing of no-load current, no-load loss, short circuit voltage, short circuit loss, and capacity
  • Automatic range switching with wide voltage and current measurement ranges
  • Three different meter testing methods
  • Automatic wiring verification and three-phase voltage/current vector diagram display
  • Full current load testing for transformers up to 1000kVA
  • Automatic correction for waveform, temperature, non-rated voltage, and non-rated current
  • High-brightness 320×240 LCD screen with brightness adjustment and touch button operation
  • User-programmable storage for 40 test sample parameters
  • Built-in real-time clock for automatic test date recording
  • Integrated thermal printer for fast result printing
  • Data storage for up to 500 test results with PC connectivity
  • Extended range measurement capability using external voltage and current transformers
Technical Specifications
Test Capabilities
  • Three-phase voltage RMS: Uab, Ubc, Uca
  • Three-phase AC voltage average values: Uab, Ubc, Uca
  • Three-phase current RMS: Ia, Ib, Ic
  • No-load loss percentage and no-load current: Po, Io%
  • Load loss, impedance voltage percentage, short circuit impedance: Pt, ekt, Zt
  • Temperature-compensated load loss and impedance measurements
  • Transformer actual capacity assessment and judgment
Environmental Conditions
Temperature-5°C to 40°C
Relative Humidity<95% (at 25°C)
Altitude<2500m
External InterferenceNo strong vibration or electromagnetic fields
Power Supply220VAC ±10%, 45Hz-55Hz
Measurement Ranges
Capacity10kV Oil-immersed/Dry-type: 30kVA-2500kVA
35kV Oil-immersed: 50kVA-31500kVA
20kV Dry-type: 50kVA-2500kVA
35kV Dry-type: 50kVA-2000kVA
Voltage0-450V (phase), 0-800V (line) with auto-ranging
Current0-100A with auto-ranging
Frequency45Hz-65Hz
Measurement Accuracy
Voltage20-100V: ±0.2%FS; 100-450V: ±(0.2%+3 digit)
Current0.5-10A: ±0.2%FS; 10-100A: ±(0.2%+3 digit)
Power±0.5% (CosΦ>0.1), ±1.0% (0.02<CosΦ<0.1)
Insulation Strength
Insulation ResistanceVoltage/current input to shell ≥100MΩ
Withstand VoltagePower supply to shell: 2kV RMS, 1 minute
Physical Specifications
Dimensions400×300×220mm
Weight12kg (accessories not included)
Product Images


MY-338 Power Quality Analyzer in use with clamp transformers
MY-338 Power Quality Analyzer measurement setup configuration
MY-338 Power Quality Analyzer detailed controls and connection ports
Buy Multi-Function Transformer Power Tester, Portable High Accuracy for Load & No-Load Test at wholesale prices
Send your message to this supplier
 
*From:
*To: Wuhan Mingyang Technology Co., Ltd
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0