Sign In | Join Free | My infospaceinc.com
infospaceinc.com
Products
Search by Category
Home >

KW2000 Intelligent Resistive Inductive Load Bank for Generator Set Testing

Categories Resistive Load Bank
MOQ: 1 Set
Delivery Time: 14 days
Color: Customized
Payment Terms: L/C,T/T
Application: Generator test
Rated Volage: 400V
Load capacity: Varies (e.g., 10kW to 2000kW)
Price: usd13,000.00
Control Power: 380 VAC 50Hz
Certification: CE, ISO
Place of Origin: CHINA
Packaging Details: wooden case
Supply Ability: 20 UNITS PER Month
Portability: Portable or Stationary
Model Number: KL200
Heat Dispersion: Air Cooling
Brand Name: Kingway Power
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

KW2000 Intelligent Resistive Inductive Load Bank for Generator Set Testing

KW2000 Intelligent Resistive Inductive Load Bank for Generator Set Testing

Our high-efficiency intelligent load banks are engineered to provide reliable, comprehensive performance testing and validation for demanding industrial power applications. By utilizing advanced resistive and inductive load control technology, our systems deliver optimized load simulation across diverse power sources, including diesel/gas generator sets, UPS systems, and micro-grids, ensuring maximum operational stability and system safety.

From factory acceptance testing (FAT) to on-site distributed power station commissioning, Kingway load testing systems integrate precision PLC steps, robust cooling architectures, and intelligent remote-monitoring software. Every unit is custom-calibrated to match specific voltage and power factor requirements ($0.8$ to $1.0$), significantly reducing the risk of power failure and wet-stacking while maximizing the long-term reliability of your energy assets.

Technical Specifications

FeatureDetailed Configuration
Rating voltage/frequency400V, 3 phase 4 wire 50Hz
Max Load Power

Apparent Power: 3500KVA

Resistive Load: 2800KW

Inductive Load: 2100KVAR

Load Resolution

Resistive Load: 22 steps 1KW,2KW,2KW,5KW,10KW,10KW,20KW,50KW,100KW,200KW,200KW,200KW,200KW,200KW,200KW,200KW,200KW,200KW,200KW,200KW, 200KW, 200KW,

Inductive Load: 19 steps

1KVAR,2 KVAR, 2KVAR, 5KVAR, 10KVAR, 10KVAR, 20KVAR, 50KVAR, 100KVAR,100KVAR, 200KVAR, 200KVAR, 200KVAR, 200KVAR, 200KVAR,200KVAR,200KVAR,200KVAR,200KVAR

Power Factor0.8(lag)
Load Tolerance (each step)±5%
Load Tolerance (overall)±3%
Fan &Control VoltageExternal AC 3 phase 4 line, 380V/50Hz
Wire Connection

Load bank input——Copper bar (star coupling ”Y”)

Control power input——Connector-bar

Communication InterfaceRS485,RS232
InsulationF
Max Protection GradeIP54
Duty CycleContinuous
CoolingForced air cooling, by Axial Fan; horizontal inlet air, vertical exhaust cooling
EnclosureContainer type,with a ladder, air inlet and outlet with mesh enclosure and protection door
Internal LightingAdequate internal lighting will be provided
TransportationHoisting, there are lifting lug in top of casing
ColorGrey RAL7035 or as required
Dimensions6058mm×2350mm×2591mm(L×W×H)
Operating Environment Parameter
WorkplaceOutdoor
Ambient Temperature-10+50
Relative Humidity≤95%
Atmospheric Pressure86106kPa
Brands of Main Components
ContactorSchneider
FuseMiro
Alloy ResistorKINGWAY
Data Processing SoftwareKINGWAY

Why Choose Our Power Systems?

  • Precision Load Calibration: Advanced PLC multi-step control with precise resistive and inductive stepping to perfectly simulate real-world power factor conditions.


  • Thermal Dynamics Integration: Heavy-duty forced-air cooling systems with optimized airflow channels and high-temperature resistant alloy elements to extend equipment service life.


  • High Asset Protection: Accurate capacity and transient response validation prevents generator wet-stacking and grid failures, ensuring high ROI by securing your critical power infrastructure.


  • Full-Lifecycle Support: Comprehensive spare parts availability, intelligent remote-monitoring compatibility, and global technical diagnostic services.


Primary Applications

  • Critical Infrastructure & Data Centers: Routine maintenance, sudden load-rejection testing, and capacity verification for backup UPS systems and standby diesel generators.

  • Marine & Shipyards: Full-load performance testing and factory acceptance testing (FAT) for shipboard power systems, marine thrusters, and offshore drilling platforms.

  • Energy & Utilities: Commissioning and periodic testing of distributed power stations, high-voltage substations, and renewable energy micro-grids (including Biogas and Natural Gas generator sets).


Frequently Asked Questions (FAQ)

Q1: How do I choose the correct generator for my gas source?

A: Gas composition and pressure are critical. Please provide a gas analysis report (including H2S content), and our engineering team will suggest the optimal model.

Q2: Can the generator operate in extreme temperatures?

A: Yes, we provide custom cooling systems, including specialized radiators or heat exchangers, for operational environments ranging from -40°C to +50°C.

Q3: How often is maintenance required?

A: Maintenance cycles depend on gas quality. We provide a tailored maintenance schedule and digital monitoring tools to track performance and predict service intervals.

Buy KW2000 Intelligent Resistive Inductive Load Bank for Generator Set Testing at wholesale prices
Send your message to this supplier
 
*From:
*To: Qingdao Kingway Industry Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)
 
Inquiry Cart 0