Sign In | Join Free | My infospaceinc.com
infospaceinc.com
Products
Search by Category
Home >

Schneider EPP302 Panel Differential Pressure Sensor 0-2500Pa No Display

Categories Room Sensors
Brand Name: Schneider
Certification: CE RoHS
MOQ: 5
Payment Terms: T/T,Western Union
Packaging Details: Carton
Place of Origin: EU
Delivery Time: 7 Days
Wiring Device Mounting: DIN rail
Dimensions: 90mm x 35mm x 60mm
Protection Rating: IP20 protection level
Switchingfrequency: Up to 60 Hz
Controlmethod: Electrical and Manual Override
Model Number: EPP302
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
Submit Buying Request
  • Product Details
  • Company Profile

Schneider EPP302 Panel Differential Pressure Sensor 0-2500Pa No Display

Schneider EPP302 Panel Differential Pressure Sensor 0-2500Pa No Display
The SpaceLogic EPP302 is a heavy-duty, panel-mount differential pressure transmitter designed to monitor pressure drops up to 2500 Pa. Operating as the high-range anchor within the micro-differential pressure EPP lineup, this device is engineered for higher static force ventilation envelopes, industrial filter bags, and centrifugal fans.
This display-less panel transmitter balances exceptional economic pricing with a certified ±1.0% FS tracking accuracy, field-selectable 4-20mA, 0-5V, and 0-10V outputs, and rugged reliability, making it the perfect companion product to the EPP301.
Technical Specifications
Protocol / CommunicationNone. Pure analog hardwired output.
I/O Points & Signals1 analog output channel. Selectable via DIP switches: 4 to 20 mA (current loop), 0 to 5 VDC, or 0 to 10 VDC. Supports on-board velocity calculation mode (0 to 30 m/s).
Power Supply / Voltage
Current output mode:12 to 30 VDC
Voltage output mode:24 VAC ±15% (50/60 Hz) or 15 to 30 VDC
Sensor Parameters & Accuracy
Measuring Range:0 to 2500 Pa. Supports sub-ranges: 0-500 Pa / 0-1000 Pa / 0-2500 Pa
Measurement Accuracy:±1.0% FS. Low-drift piezoresistive silicon core
Maximum Static Overpressure:Withstands up to 25 kPa without physical damage
Auto-Zero Calibration:Built-in on-board push-button for instant automatic zero-point drift correction
Regulatory & CertificationsUL 916, CE, RCM, FCC Class B, RoHS, REACH
Enclosure & MaterialIP65 / NEMA 4 rated polycarbonate housing with integrated brass barb fittings for 3/16" ID flexible tubing
Typical Applications
  • Multi-Stage HVAC Filtration: Monitors higher static drop points (often exceeding 1000 Pa) in industrial air-scrubbing systems and primary-to-tertiary cleanroom air-handling filter banks.
  • Heavy-Duty Exhaust Fan Safety Protection: Tracks dynamic static pressure drop across high-velocity ventilation intake points and cyclone dust collection cells to protect fan motors from surge conditions.
  • High-Velocity Air Speed Conversion: Configured in wind-speed translation mode to measure velocity ranges up to 30 m/s inside large scale cooling ducts.