| Product Series | SPEC Pak High Power |
| Current Rating (Max) | Up to 260 Amps (with 3/0 AWG) |
| Wire Size Accommodation | 24 to 3/0 AWG (0.25 to 85.0 mm) |
| Auxiliary Contacts | Up to 8 |
| Mating Cycles (Min. Average) | 1,500 |
| Connect/Disconnect Force (lbf) | 28 (125 N) |
| Operating Temperature (C) | -40 to 105 |
| Operating Temperature (F) | -40 to 221 |
| Flammability Rating (Shells) | UL94 V-0 |
| UV Rating (equivalent) | UL746C F1 |
| IP Rating | IP68 |
| Crush Test | Pass (per EIA-364-40B) |
| Drop Test | Pass (per UL50E) |
| Power Contacts: | |
| PP180 UL Current Rating (Amperes) | 260 |
| PP180 CSA (30C Rise) (Amperes) | 140 |
| PP180 Voltage Rating (AC/DC) | 600 |
| PP180 Contact Barrel Wire Size (AWG) | 3/0 to 6 |
| PP180 Contact Barrel Wire Size (mm) | 85.0 to 13.3 |
| PP180 Average Contact Resistance (milliohm) | 0.10 |
| PP180 Contact Retention Force (lbf) | 170 (756 N) |
| PP120 UL Current Rating (Amperes) | 190 |
| PP120 CSA (30C Rise) (Amperes) | 100 |
| PP120 Voltage Rating (AC/DC) | 600 |
| PP120 Contact Barrel Wire Size (AWG) | 1/0 to 6 |
| PP120 Contact Barrel Wire Size (mm) | 53.5 to 13.3 |
| PP120 Average Contact Resistance (milliohm) | 0.14 |
| PP120 Contact Retention Force (lbf) | 100 (445 N) |
| PP75 UL Current Rating (Amperes) | 70 |
| PP75 CSA (30C Rise) (Amperes) | 40 |
| PP75 Voltage Rating (AC/DC) | 600 |
| PP75 Contact Barrel Wire Size (AWG) | 6 to 12 |
| PP75 Contact Barrel Wire Size (mm) | 13.3 to 3.3 |
| PP75 Average Contact Resistance (milliohm) | 0.20 |
| PP75 Contact Retention Force (lbf) | 50 (222 N) |
| PowerMod UL Current Rating (Amperes) | 5 |
| PowerMod Voltage Rating (AC/DC) | 600 |
| PowerMod Contact Barrel Wire Size (AWG) | 12 to 24 |
| PowerMod Contact Barrel Wire Size (mm) | 4.0 to 0.25 |
| PowerMod Average Contact Resistance (milliohm) | 3.00 |
| PowerMod Contact Retention Force (lbf) | 8 (36 N) |
| Contact Mating Cycles (no load) | 10,000 |
| Housing Arrangements: | |
| H02 Arrangement | Up to two PP180 & 8 Auxiliaries |
| H03 Arrangement | Up to three PP120 & 8 Auxiliaries |
| H06 Arrangement | Up to six PP75 & 8 Auxiliaries |
| Wire Protection (Glands): | |
| PG Gland Compatibility | Size 36 & 42 |
| Types | Multi Hole Glands (Discrete Wires), Single Hole Glands (Jacketed
Cable) |
| Dimensions (Approximate): | |
| Overall Length w/ Gland (PG 36) | 155.2 mm (6.11 in) - 200 mm (7.9 in) |
| Overall Length w/ Gland (PG 42) | 155.2 mm (6.11 in) - 208 mm (8.2 in) |