| Series | ConCept 184, 185, 186 |
| Pole Numbers | 2, 3, 4, 5, 10, 20 |
| Module Types | Screw connection (2-pole), Crimp contact (3- to 20-pole), Tension
clamp (4-pole) |
| Contact Diameter (mm) | 3.6 (CM-3), 2.5 (CM-5), 1.6 (CM-10), 1 (CM-20), 2.5 (CM-HE), 2.5
(CM-4BZF/4SZF), 6 (CM-1/PE, CM-2) |
| Conductor Cross-section (mm) | 1.5...10.0 (CM-3), 0.75...4.0 (CM-5), 0.14...2.5 (CM-10),
0.08...0.52 (CM-20), 0.5...4.0 (CM-HE), 0.5...2.5 (CM-4BZF/4SZF),
4.0...16.0 (CM-1/PE, CM-2) |
| AWG Conductor | 12...7 (CM-3), 20...12 (CM-5), 26...14 (CM-10), 28...20 (CM-20),
20...12 (CM-HE), 20...12 (CM-4BZF/4SZF), 12...6 (CM-1/PE, CM-2) |
| Rated Voltage (V) | 630 (CM-3), 250* (CM-5), 250 (CM-10), 100 (CM-20), 630 (CM-HE), 400
(CM-4BZF/4SZF), 1000 (CM-1/PE, CM-2) |
| Rated Current (A) | 40 (CM-3), 20 (CM-5), 10 (CM-10), 4 (CM-20), 25 (CM-HE), 14
(CM-4BZF/4SZF), 82 (CM-1/PE, CM-2) |
| Impulse Voltage (kV) | 8 (CM-3), 6 (CM-5), 4 (CM-10), 1.5 (CM-20), 8 (CM-HE), 6
(CM-4BZF/4SZF), 6 (CM-1/PE, CM-2) |
| Pollution Severity | 3 |
| Insulation Resistance () | > 1012 (CM-3, CM-HE, CM-4BZF/4SZF, CM-1/PE, CM-2), > 1011 (CM-5, CM-10, CM-20) |
| Overvoltage Category | III |
| Through Resistance (m) | < 5 |
| Note on Voltage | *400 Volt only if black modules |
| Note on Ferrules | Required for conductors with cross-section 0.75 mm |
| Note on Ring Tongues | Required for conductors with cross-section 6 mm to 10 mm |
| Note on Module Colors | CM-HE (4-pole) and CM-4BZF/4SZF are only available in PC (grey) |